NEK 606 RFOU-HCF / TFOU-HCF Cable
NEK 606 RFOU-HCF / TFOU-HCF Cable
NEK 606 RFOU-HCF / TFOU-HCF Cable Application
These cables are fire resistant, flame retardant, low smoke and halogen free, used for emergency control, power and lighting systems that need to be operational during a 1100℃ hydrocarbon fire.NEK 606 RFOU-HCF / TFOU-HCF Cable Standards :
IEC 60092-354 - Design
IEC 60228 class 2 - Conductor
IEC 60092-351 - Insulation
IEC 60092-359 - Sheath
IEC 60332-1 - Flame Retardant
IEC 60332-3-22 - Flame Retardant
IEC 60331-21 - Fire Resistant
UL 1709 / ASTM E1529 - HC Fire resistance
IEC 600754-1,2 - Halogen Free
IEC 61034-1,2 - Low Smoke
NEK 606 RFOU-HCF / TFOU-HCF Cable Model
P30 RFOU-HCF / TFOU-HCF 6/10(12) kV
P31 RFOU-HCF / TFOU-HCF 8.7/15kV
P32 RFOU-HCF / TFOU-HCF 12/20(24) kV
P33 RFOU-HCF / TFOU-HCF 18/30(36) kV
NEK 606 P30 RFOU-HCF / TFOU-HCF Cable Construction :
1.Conductors : Circular tinned annealed stranded copper to IEC 60228 class 2.
2.Conductor Screen : Semi conducting material.
3.Insulation : Halogen-free EPR. XLPE can be offered as an option.
4.Insulation Screen : Semi conducting material and tinned copper wire braid.
5.Bedding : Halogen free compound. Armour : Tinned copper wire braid.
6.Outer Sheath1 : Halogen free thermosetting compound, SHF2, coloured red.
7.HC-fire protection : Extruded thermoplastic fire protection compound.
8.Taping : Lapped glass fibre tape.
9. Outer Sheath2 : Flame retardant halogen-free thermoplastic compound, SHF1, coloured red.
NEK 606 RFOU-HCF / TFOU-HCF Cable Electrical Characteristics :
Nominal Cross Section Area | mm² | 70 | 95 | 120 | 150 | 185 | 240 | 300 |
Nominal Conductor Diameter | mm | 10.3 | 12.2 | 13.8 | 15.1 | 17.0 | 19.6 | 21.9 |
Maximum DC Resistant@20℃ | Ω/km | 0.27 | 0.195 | 0.154 | 0.126 | 0.1 | 0.0762 | 0.0607 |
Continuous Current Rating@45℃1 Core | A | 242 | 293 | 339 | 389 | 444 | 522 | 601 |
Continuous Current Rating@45℃3 Core | A | 169 | 205 | 237 | 272 | 311 | 365 | 421 |
Short Circuit Current 1s | A | 10020 | 13590 | 17170 | 21460 | 26470 | 34340 | 42930 |
Operating Voltage | KV | 6/10 | 6/10 | 6/10 | 6/10 | 6/10 | 6/10 | 6/10 |
Ambient Temperature Correction Factors :
Ambient Temperature Correction Factors | 35 | 40 | 45 | 50 | 55 | 60 | 65 | 70 | 75 | 80 |
Rating Factor | 1.1 | 1.05 | 1.0 | 0.94 | 0.88 | 0.82 | 0.74 | 0.67 | 0.58 | 0.47 |
NEK 606 RFOU-HCF / TFOU-HCF Cable Mechanical and Thermal Properties :
1.Bending Radius : 25×OD (during installation); 12×OD (fixed installed).
2.Temperature Range : -20℃ ~ +90℃.
NEK 606 RFOU-HCF / TFOU-HCF Cable Dimensions and Weight :
Construction No. of cores×Cross section (mm²) |
Nominal Insulation Thickness mm |
Nominal Diameter Over Bedding mm |
Nominal Diameter Over Sheath1 mm |
Nominal Overall Diameter mm |
Nominal Weight kg/km |
1×70 | 3.4 | 23.5 | 30.0 | 62.0 | 5220 |
1×95 | 3.4 | 25.5 | 32.0 | 64.5 | 5900 |
1×120 | 3.4 | 27.5 | 34.0 | 66.5 | 6340 |
1×150 | 3.4 | 28.5 | 35.0 | 67.5 | 6670 |
1×185 | 3.4 | 30.5 | 36.5 | 69.0 | 7320 |
1×240 | 3.4 | 33.0 | 39.0 | 72.0 | 8250 |
1×300 | 3.4 | 35.0 | 41.5 | 74.5 | 9280 |
3×50 | 3.4 | 47.0 | 55.0 | 89.0 | 10970 |
3×95 | 3.4 | 54.0 | 62.5 | 97.0 | 14230 |
3×150 | 3.4 | 60.0 | 70.5 | 106.0 | 17400 |