TFOU P1 P8 Flame retardant mud resistant offshore power cable

TFOU P1 P8 Flame retardant mud resistant offshore power cable

TFOU P1/P8 Halogen free flame retardant mud resistant mud resistant offshore power cable

TFOU P1/P8 Halogen free flame retardant mud resistant offshore power cable application

This cable is mainly intended for power,lighting,control system of offshore units,meets the mud resistant requirements of NEK 606.

TFOU P1/P8 Halogen free flame retardant mud resistant offshore power cable standards

Design IEC 60092-353

Conductor IEC 60228

Insulation IEC 60092-351

Sheath IEC 60092-359

Flame retardant IEC 60332-3

Halogen free:IEC 60754

Low smoke:IEC 60134

Mud resistant:NEK 606

TFOU P1/P8 Halogen free flame retardant mud resistant offshore power cable structure

TFOU-P1-P8-Structure.jpg

1. Conductor stranded tinned cooper Class 2

2. XLPE insulated

3. Halogen free compound filler

4. Polyolefin inner covering

5. Tinned copper wire braid

6. Flame retardant and halogen free mud resistant thermoset compund,SHF2 outer sheath

7.Outer sheath color: Black

TFOU P1/P8 Halogen free flame retardant mud resistant offshore power cable Main Parameter

Maximum conductor temperature:+90℃

Rated Voltage:0.6/1kv

Tested Voltage:3.5kv/5min

Flame spread test on bunched cable:Category A

Smoke density of finished cable:≥60%

Bending radius : 8 × OD ( installing ); 6 × OD ( fixed installation )

TFOU P1/P8 Halogen free flame retardant mud resistant offshore power cable Technical specification

Nominal Conductor Cross-section Area mm2 1.5 2.5 4 6 10 16 25 35 50 70
Nominal Conductor Diameter mm 1.6 2.1 2.6 3.2 4.0 5.1 6.5 7.4 8.7 10.3
Maximum DC Resistance @20℃ Ω/km 12.2 7.56 4.7 3.11 1.84 1.16 0.734 0.529 0.391 0.27
Continuous rated current @45℃1Core A 23 30 40 52 72 96 127 157 196 242
Continuous rated current @45℃2Core A 20 26 34 44 61 82 108 133 167 206
Continuous rated current @45℃3&4Core A 16 21 28 36 50 67 89 110 137 169
Short-circuit current 1s A 210 360 570 860 1430 2290 3580 5010 7150 10020
Working Voltage KV 0.6/1 0.6/1 0.6/1 0.6/1 0.6/1 0.6/1 0.6/1 0.6/1 0.6/1 0.6/1

Nominal Conductor Cross-section Area mm2 95 120 150 185 240 300 400 500 630
Nominal Conductor Diameter mm 12.2 13.8 15.1 17.0 19.6 21.9 24.6 27.6 32.5
Maximum DC Resistance@20℃ Ω/km 0.195 0.154 0.126 0.1 0.0762 0.0607 0.0475 0.0369 0.0286
Continuous rated current @45℃1Core A 293 339 389 444 522 601 690 780 890
Continuous rated current @45℃2Core A 249 288 331 444 444 511 587 663 757
Continuous rated current @45℃3&4Core A 205 237 272 311 365 421 483 546 623
Short-circuit current 1s A 13590 17170 21460 26470 34340 42930 57230 71540 90140
Working Voltage KV 0.6/1 0.6/1 0.6/1 0.6/1 0.6/1 0.6/1 0.6/1 0.6/1 0.6/1

Ambient temperature correction factor

Ambient temperature correction factor 35 40 45 50 55 60 65 70 75 80
Rated Factor 1.1 1.05 1.0 0.94 0.88 0.82 0.74 0.67 0.58 0.47