BFOU P5 P12 Halogen free mud resistant offshore power cable

BFOU P5 P12 Halogen free mud resistant offshore power cable

BFOU P5/P12 Halogen free mud resistant offshore power cable

BFOU P5/P12 Halogen free mud resistant offshore power cable application

This cable is mainly intended for power,lighting,control system of offshore units,meets the mud resistant requirements of NEK 606.

BFOU P5/P12 Halogen free flame retardant mud resistant offshore power cable standards

Design IEC 60092-353

Conductor IEC 60228

Insulation IEC 60092-351

Sheath IEC 60092-359

Flame retardant IEC 60332-3

Halogen free:IEC 60754

Low smoke:IEC 60134

Mud resistant:NEK 606

BFOU P5/P12 Halogen free flame retardant mud resistant offshore power cable structure

BFOU-P5-P12-Structure.jpg

1. Conductor stranded tinned cooper Class 2

2. Mica tape and EPR insulated or Mica tape and XLPE insulated

3. Halogen free compound filler

4. Polyolefin inner covering

5. Tinned copper wire braid

6. Flame retardant and halogen free mud resistant thermoset compund,SHF2 outer sheath

7. Outer sheath color: Black

BFOU P5/P12 Halogen free flame retardant mud resistant offshore power cable Main Parameter

Maximum conductor temperature:+90℃

Rated Voltage:0.6/1kv

Tested Voltage:3.5kv/5min

Flame spread test on bunched cable:Category A

Smoke density of finished cable:≥60%

Bending radius : 8 × OD ( installing ); 6 × OD ( fixed installation )

BFOU P5/P12 Halogen free flame retardant mud resistant offshore power cable Technical specification

Nominal Cross Section Area mm2 1.5 2.5 4 6 10 16 25 35 50
Nominal Diameter mm 1.6 2.1 2.6 3.2 4.0 5.1 6.5 7.4 8.7
Maximum DC Resistance @20℃ Ω/km 12.2 7.56 4.7 3.11 1.84 1.16 0.734 0.529 0.391
Continuous rated current @45℃1Core A 23 30 40 52 72 96 127 157 196
Continuous rated current @45℃2Core A 20 26 34 44 61 82 108 133 167
Continuous rated current @45℃3&4Core A 16 21 28 36 50 67 89 110 137
Short Circuit Current 1s A 210 360 570 860 1430 2290 3580 5010 7150
Working Voltage KV 0.6/1 0.6/1 0.6/1 0.6/1 0.6/1 0.6/1 0.6/1 0.6/1 0.6/1

Nominal Cross Section Area mm2 70 95 120 150 185 240 300 400 630
Nominal Diameter mm 10.3 12.2 13.8 15.1 17.0 19.6 21.9 24.6 32.5
Maximum DC Resistance@20℃ Ω/km 0.27 0.195 0.154 0.126 0.1 0.0762 0.0607 0.0475 0.0286
Continuous rated current @45℃1Core A 242 293 339 389 444 522 601 690 890
Continuous rated current @45℃2Core A 206 249 288 331 444 444 511 587 757
Continuous rated current @45℃3&4Core A 169 205 237 272 311 365 421 483 623
Short Circuit Current 1s A 10020 13590 17170 21460 26470 34340 42930 57230 90140
Working Voltage KV 0.6/1 0.6/1 0.6/1 0.6/1 0.6/1 0.6/1 0.6/1 0.6/1 0.6/1

Ambient temperature correction factor

Ambient temperature correction factor 35 40 45 50 55 60 65 70 75 80
Rated Factor 1.1 1.05 1.0 0.94 0.88 0.82 0.74 0.67 0.58 0.47

BFOU P5/P12 Halogen free flame retardant mud resistant offshore power cable Show

BFOU P5 P12 Show.jpg

CONTACT WITH US NOW

Our mail: manager@hiseamarine.com

Society certificates

Hi-Sea Group-Obtained-certification