FX-TFOI VFD Cable standards

- Design guide : IEC 60092-350 & IEC 60092-353

- Insulation material : IEC 60092-351, XLPE
- Sheath material : IEC 60092-359, SHF1
- Flame retardant : IEC 60332-1 & IEC 60332-3 Category A
- Halogen content : IEC 60754-1, 0.5%
- Smoke emission : IEC 61034, 60%
- Cold bend/impact : CSA 22.2 No. 0.3 (-40° / -35° )

- Max. rated conductor temperature : 90°℃

FX-TFOI VFD Cable construction

Classification Code Construction detail
Conductor FX

- Stranded plain annealed copper wires as per IEC 60228, Class 5

- A suitable tape may be applied on the conductor

Insulation T - XLPE as per IEC 60092-351
Cabling
- Insulated conductors shall be cabled

- Flame retardant & non-hygroscopic fillers may be used

- Suitable tape(s) may be applied on the cabled core

- A Filler may be applied to obtain a circular Cable
Inner covering F Non-hygroscopic material
Armor(Screen) (VFD) - CU/PS Tape providing 100% Coverage
O - Braid of plain annealed copper wire
- Coverage density : Min. 90%
Sheath I

- SHF1 as per IEC 60092-359

- Sheath color : Black