BFOU Halogen free flame retardant offshore power cable

BFOU Halogen free flame retardant offshore power cable

BFOU Halogen free flame retardant offshore power cable

BFOU Halogen free flame retardant offshore power cable application

This cable is mainly intended for power,lighting,control system of offshore units,exclude mud condition.

BFOU Halogen free flame retardant offshore power cable standards

Design IEC 60092-353

Conductor IEC 60228

Insulation IEC 60092-351

Sheath IEC 60092-359

Flame retardant IEC 60332-3

Halogen free:IEC 60754

Low smoke:IEC 60134

BFOU Halogen free flame retardant offshore power cable structure

1. Conductor stranded tinned cooper Class 2

2. Mica tape and EPR insulated or Mica tape and XLPE insulated

3. Halogen free compound filler

4. Polyolefin inner covering

5. Tinned copper wire braid

6. Flame retardant and halogen free thermoset compund,SHF2 outer sheath

7.Outer sheath color: Black

BFOU Halogen free flame retardant offshore power cable Core Identification

1 Core:Red

2 Cores:Red Blue

3 Cores:Red Green Yellow

4 Cores:Red Green Yellow Blue

5 Cores and above:Black and White printed numbers

BFOU Halogen free flame retardant offshore power cable Main Parameter

Maximum conductor temperature:+90℃

Rated Voltage:0.6/1kv

Tested Voltage:3.5kv/5min

Flame spread test on bunched cable:Category A

Smoke density of finished cable:≥60%

Bending radius : 8 × OD ( installing ); 6 × OD ( fixed installation )

BFOU Halogen free flame retardant offshore power cable Technical specification

Nominal Cross Section Area
mm2
1.5
2.5
4
6
10
16
25
35
50
Nominal Conductor Diameter
mm
1.6
2.1
2.6
3.2
4.0
5.1
6.5
7.4
8.7
Maximum DC Resistance @20℃
Ω/km
12.2
7.56
4.7
3.11
1.84
1.16
0.734
0.529
0.391
Continuous rated current @45℃ 1 Core
A
23
30
40
52
72
96
127
157
196
Continuous rated current @45℃ 2Cores
A
20
26
34
44
61
82
108
133
167
Continuous rated current @45℃ 3&4Cores
A
16
21
28
36
50
67
89
110
137
Short circuit current 1s
A
210
360
570
860
1430
2290
3580
5010
7150
Working Voltage
KV
0.6/1
0.6/1
0.6/1
0.6/1
0.6/1
0.6/1
0.6/1
0.6/1
0.6/1

Nominal Cross Section Area
mm2
70
95
120
150
185
240
300
400
630
Nominal Conductor Diameter
mm
10.3
12.2
13.8
15.1
17.0
19.6
21.9
24.6
32.5
Maximum DC Resistance@20℃
Ω/km
0.27
0.195
0.154
0.126
0.1
0.0762
0.0607
0.0475
0.0286
Continuous rated current @45℃ 1 Core
A
242
293
339
389
444
522
601
690
890
Continuous rated current @45℃ 2 Cores
A
206
249
288
331
444
444
511
587
757
Continuous rated current @45℃ 3&4 Cores
A
169
205
237
272
311
365
421
483
623
Short circuit current 1s
A
10020
13590
17170
21460
26470
34340
42930
57230
90140
Working Voltage
KV
0.6/1
0.6/1
0.6/1
0.6/1
0.6/1
0.6/1
0.6/1
0.6/1
0.6/1

Ambient temperature correction factor

Ambient temperature correction factor
35
40
45
50
55
60
65
70
75
80
Rated Factor
1.1
1.05
1.0
0.94
0.88
0.82
0.74
0.67
0.58
0.47

BFOU Halogen free flame retardant offshore power cable Show

BFOU.jpg

CONTACT WITH US NOW

Our mail: manager@hiseamarine.com

Society certificates

Hi-Sea Group-Obtained-certification