- Home
- > Cable
- > Marine Cable
BFOU Halogen free flame retardant offshore power cable
BFOU Halogen free flame retardant offshore power cable
BFOU Halogen free flame retardant offshore power cable application
This cable is mainly intended for power,lighting,control system of offshore units,exclude mud condition.
BFOU Halogen free flame retardant offshore power cable standards
Design IEC 60092-353
Conductor IEC 60228
Insulation IEC 60092-351
Sheath IEC 60092-359
Flame retardant IEC 60332-3
Halogen free:IEC 60754
Low smoke:IEC 60134
BFOU Halogen free flame retardant offshore power cable structure
1. Conductor stranded tinned cooper Class 2
2. Mica tape and EPR insulated or Mica tape and XLPE insulated
3. Halogen free compound filler
4. Polyolefin inner covering
5. Tinned copper wire braid
6. Flame retardant and halogen free thermoset compund,SHF2 outer sheath
7.Outer sheath color: Black
BFOU Halogen free flame retardant offshore power cable Core Identification
1 Core:Red2 Cores:Red Blue
3 Cores:Red Green Yellow
4 Cores:Red Green Yellow Blue
5 Cores and above:Black and White printed numbers
BFOU Halogen free flame retardant offshore power cable Main Parameter
Maximum conductor temperature:+90℃
Rated Voltage:0.6/1kv
Tested Voltage:3.5kv/5min
Flame spread test on bunched cable:Category A
Smoke density of finished cable:≥60%
BFOU Halogen free flame retardant offshore power cable Technical specification
Nominal Cross Section Area |
mm2
|
1.5
|
2.5
|
4
|
6
|
10
|
16
|
25
|
35
|
50
|
Nominal Conductor Diameter |
mm
|
1.6
|
2.1
|
2.6
|
3.2
|
4.0
|
5.1
|
6.5
|
7.4
|
8.7
|
Maximum DC Resistance @20℃ |
Ω/km
|
12.2
|
7.56
|
4.7
|
3.11
|
1.84
|
1.16
|
0.734
|
0.529
|
0.391
|
Continuous rated current @45℃ 1 Core |
A
|
23
|
30
|
40
|
52
|
72
|
96
|
127
|
157
|
196
|
Continuous rated current @45℃ 2Cores |
A
|
20
|
26
|
34
|
44
|
61
|
82
|
108
|
133
|
167
|
Continuous rated current @45℃ 3&4Cores |
A
|
16
|
21
|
28
|
36
|
50
|
67
|
89
|
110
|
137
|
Short circuit current 1s |
A
|
210
|
360
|
570
|
860
|
1430
|
2290
|
3580
|
5010
|
7150
|
Working Voltage |
KV
|
0.6/1
|
0.6/1
|
0.6/1
|
0.6/1
|
0.6/1
|
0.6/1
|
0.6/1
|
0.6/1
|
0.6/1
|
Nominal Cross Section Area |
mm2
|
70
|
95
|
120
|
150
|
185
|
240
|
300
|
400
|
630
|
Nominal Conductor Diameter |
mm
|
10.3
|
12.2
|
13.8
|
15.1
|
17.0
|
19.6
|
21.9
|
24.6
|
32.5
|
Maximum DC Resistance@20℃ |
Ω/km
|
0.27
|
0.195
|
0.154
|
0.126
|
0.1
|
0.0762
|
0.0607
|
0.0475
|
0.0286
|
Continuous rated current @45℃ 1 Core |
A
|
242
|
293
|
339
|
389
|
444
|
522
|
601
|
690
|
890
|
Continuous rated current @45℃ 2 Cores |
A
|
206
|
249
|
288
|
331
|
444
|
444
|
511
|
587
|
757
|
Continuous rated current @45℃ 3&4 Cores |
A
|
169
|
205
|
237
|
272
|
311
|
365
|
421
|
483
|
623
|
Short circuit current 1s |
A
|
10020
|
13590
|
17170
|
21460
|
26470
|
34340
|
42930
|
57230
|
90140
|
Working Voltage |
KV
|
0.6/1
|
0.6/1
|
0.6/1
|
0.6/1
|
0.6/1
|
0.6/1
|
0.6/1
|
0.6/1
|
0.6/1
|
Ambient temperature correction factor
Ambient temperature correction factor |
35
|
40
|
45
|
50
|
55
|
60
|
65
|
70
|
75
|
80
|
Rated Factor |
1.1
|
1.05
|
1.0
|
0.94
|
0.88
|
0.82
|
0.74
|
0.67
|
0.58
|
0.47
|
CONTACT WITH US NOW