110kV XLPE Insulated Power Cable

110kV XLPE Insulated Power Cable

110kV XLPE Insulated Power Cable

110kV XLPE Insulated Power Cable standard

The product is made and tested according to the enterprise standard Q/VAMT20-2007“rated voltage 110 kV cross-linked polyethylene insulated power cables and accessories”, among which, the insulation eccentricity of power cables shall be no more than 8%, partial discharge in the routine test shall be no more than 5pC and scraped finish test of extrusion conducting layer is added in the type test. The above indexes are all above the national standard GB/T11017-2002“rated voltage 110 kV cross-linked polyethylene insulated power cables and accessories” and IEC 60840:1999“Test methods and requirements of rated voltage above 30 kV(Um=36 kV)and 150 kV(Um=170 kV) extrusion-coated insulated cables and accessories”.

110kV XLPE Insulated Power Cable application

1) During the normal operation of cables, the max permissible continuous operating temperature of conductor shall not exceed 90℃;
2) Conductor short-circuit temperature not exceed 250℃, max sustaining period not exceed 5 seconds;
3) The min permissible bending radius during the cable laying is normally 25 times of the diameter of cables.
4) Free from restrictions of level difference along the route during the cable laying;
5) Pre-heated is needed when the temperature is below 0℃ during the cable laying.

110kV XLPE Insulated Power Cable Model

Type Description Scope of application
Copper core Aluminium core
YJLW02 YJLW02 XLPE insulated welding corrugated aluminium-sheathing PVC sheathed power cable The cable can be laid in tunnels or pipelines, and is equipped with better radial water-resistant performance and can bear certain pressure.
YJLW03 YJLW03 XLPE insulated welding corrugated aluminium-sheathing polyethylene sheathed power cable
YJLW02-Z YJLW02-Z Longitudinal water-resistant power cable of XLPE insulated welding corrugated aluminium-sheathing PVC sheathed The cable can be laid in tunnels or pipelines, and is equipped with better radial and longitudinal water-resistant performance and can bear certain pressure.
YJLW03-Z YJLW03-Z Longitudinal water-resistant power cable of XLPE insulated welding corrugated aluminium-sheathing polyethylene sheathed
Note: XLPE--YJ Copper conductor--T(Omitted) Aluminium conductor--L Corrugated aluminium sheath--LW PVC sheath--02 PE sheath--03 Longitudinal water resistant structure--Z

110kV XLPE Insulated Power Cable Show

ultra high voltage cable.jpg

If you need more information,please feel free to contact me,I will try all my best to help you out.

Hit Me to get more information!

CONTACT WITH US NOW

Our mail: manager@hiseamarine.com

Society certificates

Hi-Sea Group-Obtained-certification