Mobile Metal Shielded Monitor Cable

Mobile Metal Shielded Monitor Cable

Mobile Metal Shielded Monitor Cable

1.rated voltage 3.6/6kv,6/10kv,8.7/10kv,used to power mobile underground voltage changer and all similar Equipment.
2.maximum allowable conductor temperature: 65 ℃ 90 ℃
3.Permissible minimum working temperature is -35 ℃
4.cable bend radius less than six times the cable diameter.

If you feel this is not what you are looking for,please kindly check more Mobile cable here,also you can check more cable here,or you can use the search form on the upper right corner.

Mobile Metal Shielded Monitor Cable Model

Model Product Name Application
MYPTJ-3.6/6 Mine Mobile Metal Shield Monitor Rubber Sheath Flexible Cable Power Connection for Variety of Underground Voltage Changer and Similar equipment rated voltage 3.6/6kv
MYPTJ-6/10 Mine Mobile Metal Shield Monitor Rubber Sheath Flexible Cable
Power Connection for Variety of Underground Voltage Changer and Similar equipment rated voltage 6/10kv
MYPTJ-8.7/10 Mine Mobile Metal Shield Monitor Rubber Sheath Flexible Cable
Power Connection for Variety of Underground Voltage Changer and Similar equipment rated voltage 8.7/10kv

Movable Metal Shielding Monitoring Flexible Cable Specifications:

Rated Voltage 3.6/6kv cable specifications:

Core Numer*Conductor Nominal Section(mm2) Nominal Thickness(mm)
Cable Outer Diameter(mm)
Power Core Earth Core Monitoring Core Power Core Insulator Inner Sheath Outer Sheath Rated Voltage 3.6/6kv
3*25 3*16/3 3*2.5 4.0 2.5 5.5 61.0~69.0
3*35 3*16/3 3*2.5 4.0 2.5 5.5 63.5~72.0
3*50 3*16/3 3*2.5 4.0 2.5 5.5 67.5~76.0
3*70 3*25/3 3*2.5 4.0 3.0 5.5 72.5~82.0
3*95 3*35/3 3*2.5 4.0 3.0 5.5 77.0~87.0
3*120 3*35/3 3*2.5 4.0 3.0 5.5 80.5~90.0
3*150 3*50/3 3*2.5 4.0 3.0 5.5 84.5~94.5
Note:Earth Core Cross-Section is the smallest,No assessment about Inner sheath.

Rated Voltage 6/10kv cable specifications:

Core Numer*Conductor Nominal Section(mm2) Nominal Thickness(mm)
Cable Outer Diameter(mm)
Power Core Earth Core Monitoring Core Power Core Insulator Inner Sheath Outer Sheath Rated Voltage 6/10kv
3*25 3*16/3 3*2.5 4.5 2.5 5.5 63.0~71.0
3*35 3*16/3 3*2.5 4.5 2.5 5.5 66.0~74.5
3*50 3*16/3 3*2.5 4.5 3.0 5.5 70.5~79.5
3*70 3*25/3 3*2.5 4.5 3.0 5.5 74.5~84.0
3*95 3*35/3 3*2.5 4.5 3.0 5.5 79.5~88.5
3*120 3*35/3 3*2.5 4.5 3.0 5.5 82.5~92.0
3*150 3*50/3 3*2.5 4.5 3.0 5.5 86.5~96.5
Note:Earth Core Cross-Section is the smallest,No assessment about Inner sheath.

Rated Voltage 8.7/10kv cable specifications:

Core Numer*Conductor Nominal Section(mm2) Nominal Thickness(mm)
Cable Outer Diameter(mm)
Power Core Earth Core Monitoring Core Power Core Insulator Inner Sheath Outer Sheath Rated Voltage 8.7/10kv
3*25 3*16/3 3*2.5 5.5 2.5 5.5 67.0~76.0
3*35 3*16/3 3*2.5 5.5 3.0 5.5 71.0~80.0
3*50 3*16/3 3*2.5 5.5 3.0 5.5 75.0~84.5
3*70 3*25/3 3*2.5 5.5 3.0 5.5 79.0~88.0
3*95 3*35/3 3*2.5 5.5 3.0 5.5 83.5~93.0
3*120 3*35/3 3*2.5 5.5 3.0 5.5 86.5~96.5
3*150 3*50/3 3*2.5 5.5 3.0 5.5 91.0~101.5
Note:Earth Core Cross-Section is the smallest,No assessment about Inner sheath.


Insulating Restistance

Conductor Nominal Cross-Section(mm2) 20℃ Power Core Insulator Resistance Minimum (MΩ.Km) 20℃Earth Core Conductor DC Resistance Maximum (Ω/km)
Rated Voltage 3.6/6kv Rated Voltage 6/10kv Rated Voltage 8.7/10kv
16 - - - 2.31
25 650 700 1250 1.48
35 550 650 1150 1.05
50 500 550 1000 0.731
70 450 500 900 0.515
95 400 450 800 -
120 350 400 750 -
150 350 350 700 -

Movable Metal Shielding Monitoring Flexible Cable Structure

movable-metal-shielding-monitoring-flexible-cable-structure.jpg

Movable metal shielding Monitoring flexible cable show:

cable in stock3.jpg

Finished Cable

cable working.jpg

Cable Workshop

CONTACT WITH US NOW

Our mail: manager@hiseamarine.com

Society certificates

Hi-Sea Group-Obtained-certification